Home > Products > Glycol air-cooled Screw Chiller >

Screw Type Air-cooled Glycol Chiller HTSL-280AD

Screw Type Air-cooled Glycol Chiller HTSL-280AD

Screw Type Air-cooled Glycol Chiller HTSL-280AD
Screw Type Air-cooled Glycol Chiller HTSL-280ADScrew Type Air-cooled Glycol Chiller HTSL-280ADScrew Type Air-cooled Glycol Chiller HTSL-280ADScrew Type Air-cooled Glycol Chiller HTSL-280ADScrew Type Air-cooled Glycol Chiller HTSL-280AD
CategoriesGlycol air-cooled Screw Chiller
AlbumView larger image
BrandHERO-TECH
ModelScrew type Air-cooled Glycol Chiller HTSL-280AD
Compressor brandHANBELL/BITZER
Compressor typesemi-hermetic screw compressor
FanLow noise
Power3ph 380v 50hz and 60HZ for option
Temperature displayTOUCH SCREEN
Temperature range-35C to 5C
RefrigerantR22, R407C, R404A
ControlSIEMENS PLC
FOB portSHENZHEN or any pointed port in China
Terms of PaymentL/C, D/P, Western Union, T/T
Update Time2019-01-20
Detail Information

HERO-TECH 280HP air cooled glycol chiller with SCREW COMPRESSOR


HERO-TECH Air cooled glycol chillers with featured advantages as following,

l  Low cost

l  Energy saving

l  Easy connection

l  Easy and convenient maintenance

 

l  Power:3PH 380-415V 50HZ

Well Known Brand Compressor

¨      Unit adopts Germany BITZER or Taiwan HANDBELL brand semi-hermetic screw compressor. The latest 5 to 6 patented screw rotor profile with excellent efficiency.

¨      Adjustable infinite or closely stepped capacity control, features energy efficient, stable and quiet running.

¨      Most advanced patented highest precision manufacturing process.

¨      Built-in full intelligent monitoring andprotection including thermal motor temperature monitoring, phase sequencemonitoring, manual reset lock-out, oil temperature sensor.

¨      Wide range of refrigerant for option, including R22 and R404a, R407c.

Microprogramming Control System

¨      Industrial PLC centralized control combined withcompressor capacity control system, precisely monitor.

¨      Integrated protection for low temperature,high/low pressure, anti-freezing, phase missing, anti-phase, overload, motorover temperature, oil differential, flow switch, start up latency.

¨      Optional operation language, menu leading, unitrunning state easy to adjust.

Easy Installation,Reliable Running

¨      Closely stepped start-up, minimize impact toelectricity.

¨      Steady and safe running, low vibration, easy forinstallation.

¨      Compact structure, less space demand and lightin weight, easy for transport and installation.

¨      Completely wired, inspected and testedpre-delivery, saving installation time and cost.

 


l  3PH 220V/240V/380V/440V/480V/560V 60HZ

l  R410A, R134A for option

l  Running under above 40C high ambient temperature

 Soft starting

l  Plate heat exchanger

l  Electronic expansion valve

l  Nonferrous water loop

l  Pump: Minamoto Iron pump or high pressure pump


Specification for Air cooled screw chiller glycol solution 

HTSL-ASeries Low Temperature Screw Type Chiller Technical Specifications

Model

HTSL-280AD

Nominal cooling capacity

    -10℃

KW

478

    -20℃

318

    -30℃

236

Input power

KW

285

Power source

 

3PH  380V~415V/50HZ

Refrigerant

Type

 

R22/R404A

Charge

kg

218

Control

 

Thermostatic expansion valve

Compressor

Type

 

Semi-hermetic screw

Motor Power

kw

133×2

Start mode

 

Y-△

Capacity control

%

0-25-50-75-100

Evaporator

Type

 

Shell and tube

Coolant volume

-10℃

 

m3/h

82.2

-20℃

54.7

-30℃

                             40.6

Water pressure drop

KPa

48

Pipe connection

Inch

8

Condenser

Type

 

Air cooled type high efficiency finned copper tube

Fan information

Type

 

Big volume & low noise axil fan

Motor power

KW

1.2×16

Air volume

m3/h

210000

Safety devices

Inner thermostat for compressor motor, unit overload relay, high&low pressure switch,  freeze protection thermostat, reverse phase protection relay, discharge gas thermostat, flow switch.

Dimension

Length

mm

10500

Width

mm

2200

Height

mm

2350

Net weight

KG

5550

Running weight

KG

6150

           

NOTE:The specifications based on the following design conditions:

l  Condensingtemperature: 50

l  Cooling airinlet/outlet temperature: 30/38

Wereserve the right to modify the specifications without further notice.

 






Pre-sale service


1.      Professional and technical consultation and communication

2.      Equipment selection and calculation

3.      Product application solutions recommendations

4.      Engineering solutions.

 

In- Sale service


1.      3Steps quality control: IQC, PQC, OQC

2.      Provides timely installation and operation guidance

3.      Chiller commissioning according to requirements

4.      100% on-time delivery

 

After-sale service


1.      12months guarantee for all products

2.      Within warranty, any problem caused by defects of chiller itself, service offered tillthe problem solved.

3.      Service call replied immediately, solution offered within 4hours, whatever daytime ornight.

4.      Ensuring replaced parts or updated parts can be used for sold chillers,



We attend worldwide exhibitions, you can see us in your country especially on Plastic industries' exhibitions.




Please send your message to us
*We will reply your inquiry to this Email as soon as we see it
*Email
Name
Tel
*Title
*Content

Agree to use terms of service